제어알고리즘을 적용한 열회복방식 항온항습기
차인수, 하민호, 정경환 · 한국태양에너지학회 춘계학술발표회 논문집 · 2016
This study is an energy-saving HEAT RECOVERY TYPE can be used for maximum cooling capacity less power. Condenser uses the waste heat of the heating heat source, so as to have a more precise control function control algorithm are applied to design a fuzzy PID controller. This study produced a constant temperature and humidity chamber with power savings through heat recovery method to test results conversion efficiency of 95% or more features, power recovery is less than 5sec, stop delay is less than 30sec, the pump-down 10sec, pump delay 5sec, Heating delay 5sec, temperature deviation ± 2 ℃ has the (cooling deviation: 2 ℃: 2 ℃, heating deviation), humidity variation is ± 5% (3.0% deviation humidifying, dehumidifying deviation 3.0%).
Cited by 0 works.