변유량 펌프시스템에서 차압센서 위치에 따른 에너지 절감량 비교실험

경도현, 이근휘, 권정태 et al. · 대한설비공학회 2016년도 하계학술발표대회 · 2016

In case of Central heating facility like as Distric heating user’s facility, Variable speed drives are commonly used to control the speed of pumps. The use of variable speed controlled pumps instead of valve adjustment like as DPV has shown to reduce the energy consumption of pumps. but if the idea to control speed of pumps isn’t effective operation, the expansive variable speed drives cannot reduce electric energy cost. In this study the actual energy consumption of heating circulation pump with different installation position of differential pressure transmitters are compared. A variable speed control using differential pressure at the long-distance building and that at the facility room was applied to experimental field. From the experimental results, it was concluded that by using the variable speed control with the long-distance building △p setting(0.6bar), the energy consumption was reduced by up to 72.6% in comparison of constant speed control. On the other hand it was concluded that by using the variable speed control with the facility room △p setting(0.8bar), the energy consumption was reduced by up to 59.5% in comparison of constant speed control. Therefore, the variable speed control using the differential pressure at the long-distance building is recommendable.