캐스케이드 제습 냉방 시스템의 증발식 응축기에 대한 실험적 연구

박보근, 최선, 이대영 · 대한설비공학회 2016년도 하계학술발표대회 · 2016

The objective of this study is to analyze a performance of evaporative condenser and propose a quantitative value to improves the evaporative performance. The experiment variable was a refrigerant mass flow rate that was varied between 1.70 and 2.06 g/s. The inlet temperature, humidity and flow rate was fixed for the air side. The air-side evaporative performance was analyzed using the absolute and relative humidity and sub cooling. The heat balance range for the experiment was 94.2 - 97.5% with mass flow rate. In result, outlet humidity for air side was increased 79 - 80 %. Heat transfe rate was increased 4.4 - 5.1 kW by increasing the mass flow rate. Outlet humidity was required about 81.5 - 89.8 with mass flow rate variable for increasing the evaporative performance. This value was increased by 2.9 - 6.5% compared to the experimental result.