방풍재 적용에 따른 노후 창호 기밀성능 개선 효과 분석

이수인, 최현중, 최경석 et al. · 대한설비공학회 2016년도 하계학술발표대회 · 2016

Building energy loss due to infiltration was found to be 30% or more. Therefore, It is necessary to consider airtightness performance when retrofitting the building. The purpose of in this paper is to measure and analyze the airtightness performance improvement effectiveness in old window by applying of windbreak for airtightness performance betterment. The airtightness performance of windows was measured using a pressure box method. As a result, Quantity of airflow of single sliding window is 3.72 ㎥/(h·㎡) at 10 Pa. And the value is 4 class on a basis of KS F 2292. After the windbreak is attached, Quantity of airflow of single sliding window became 0.48 ㎥/(h·㎡) and was grade first class. Field measurement was carried out by using blower door. The result is as follows. The airtightness performance of subject room(ACH50 : Air change per hour at 50 Pa) is 8.21h-1. After attaching the windbreak, the airtight performance of room became 5.85h-1 that was improved 2.36h-1.

Cited by 1 works.