가스절연개폐장치에서 결함별 부분방전의 특성
박경수, 김선재, 왕국명 et al. · 한국철도학회 학술발표대회논문집 · 2016
This paper described characteristics of partial discharge(PD) depending on defects for the purpose of condition monitoring of gas insulated switchgears(GIS). Four types of defects were fabricated and PD pulses were detected using an ultra-high frequency(UHF) sensor, which had a frequency range of 300MHz~1.4GHz. The characteristics depending on defects were analyzed by phase resolved partial discharge(PRPD) method. In addition, the discharge inception voltage(DIV), discharge extinction voltage(DEV), as well as pulse magnitude and count were measured. The DIV of particle on spacer(POS) was the highest whereas that of free particle(FP) was the lowest. More than 80% of PD pulses distributed in the positive and negative half in protrusion on conductor(POC) and protrusion on enclosure(POE), respectively. From the results, clusters formed by PRPD presented different patterns depending on defects, which can be used for condition monitoring of GIS.
Cited by 0 works.