Области колебательной устойчивости изолированной системы из двух станций при вариации характеристики и мощности нагрузки

Голов Валерий Павлович, Москвин Илья Александрович, Russian Federation · 2015

Background: The flexible alternating current transmitssion system (FACTS) technology was developed in response to the problems arising when the series compensation factor is above 50%. Many investigations such as those by V.A. Venikov, V.A. Stroev, Ju.G. Shakaryan, V.K. Fokin, G.K. Zarudsky were devoted to the problem of steady-state stability loss caused by these conditions. Most of the investigations deal with a simple electrical power system with an infinite bus. Hence, it is reasonable to study the oscillatory steady-state stability of an electrical power system containing two stations of comparable power capacity with an interconnection consisting of controlled series capacitors under load capacity and power factor variations. Materials and methods: A.M. Lyapunov’s first approximation method and one parameter D-decomposition method were used. Results: The influence of load capacity and power factor on the type and shape of oscillatory stability regions has been analysed. The study has determined the range of permissible variation of controlled series capacitor regulation factor enabling oscillatory stability retention at various load capacity and power factor values. It is shown that the type of stability region has no effect on regulation factor permissible variation range. Conclusions: The choice of series compensation control factor must be carried out at the maximum transmission power of transmission lines.

Cited by 0 works.