사무소 건물의 건축 및 설비조건에 따른 에너지원단위 민감도분석
이태철, 김상옥, 여인애 et al. · 대한건축학회지회연합회 논문집 · 2011
There has been rising interests and investments worldwide in energy savings and low carbon energy by the international agreement with climate change. Energy consumption unit is necessary for planning of rational energy supply and effective energy management from the building level to urban level. Developed countries like United States, Japan, EU have constructed energy consumption DB to a certain degrees. In this study, energy sensitivity analysis of an office building with changing building envelope conditions and building equipment composition was conducted using energy consumption unit simulation tool. The results are as follows. 1) There was few difference under 5[Mcal/㎡·yr] by the kind of outer wall types. 2) Energy consumption unit difference by air volume change was 1.07~1.19 times greater at constant air volume than at variable one. Energy consumption unit combined with glass types and air-conditioning system or thermal storage system appeared to be decreased 2~3times as using higher performance glass. In other words, selecting higher performance glass helps gaining great energy efficiency in curtain wall office buildings and energy conservation will be maximized by the adaptation of low energy consuming air-conditioning system.