가스계소화설비의 소화약제 누기 감시장치에 관한 기초연구

고아라, 박정화, 박세훈 et al. · 대한설비공학회 2016년도 하계학술발표대회 · 2016

The Current Fire protection law provides where the fire protection zone over 300m2 which are Elecrical room, Generator room, Computer room in addition to that room for use similar purpose. However, where the place people lives, Gas fire extinguisher system can not install caused by its dangerousness. Even if its dangerousness, when it needs to check up people who can check gas system should go in to the Gas extinguisher room. When they checks up the amount of gas extinguisher, they use a balance for check its weight, or a level meter. These methods need to not only many people to check up, but also make accident caused by human error. So in this study we developed monitor equipment that checks up leak of gas pressure automatically, and tested its basic qualification, and environment qualification. As a result, after high temperature and low temperature test, it still works normally on lowest pressure 0.3 bar.