Ламинарный поток стерильного воздуха и ультрафиолетовое облучение в ортопедических операционных

S.V. Vasiuk, Я. Н. Васильчишин, В Л Васюк · TRAUMA · 2013

The aim of this study is to compare the effectiveness of air disinfection in orthopedic operating rooms by the method of highly effective air filtration and ultraviolet radiation (UVR). The authors carried out the study of the qualitative and quantitative composition of the air and the dynamics of these parameters in two operating rooms. In the first one the air was disinfected by method of highly effective filtration, in the second one — with the help of ultraviolet lamp. Total air contamination is operating rooms with its high filtration system is 60 times lower than in the operating rooms, in which for air disinfection UVR is used. In comparison with operating rooms, in which for air disinfection UVR is used, operating rooms with air filtration system does not contain potentially pathogenic species that can cause post-operative wounds abscess. The method of air filtration to disinfect it has some major advantages: improves species composition of microflora — in the air types that can cause purulent-inflammatory diseases are not defined; the air is not only cleaned and disinfected, but also air-conditioned, resulting in improved working conditions for staff (and prevention of various complications); microbiological parameters of air quality are maintained at a high level throughout the working hours; disinfection and cleaning of air is carried out in the presence of the staff and the patient.

Cited by 0 works.