단열재 방사율 특성을 고려한 배관 단열 기준 연구

최승혁, 윤희원, 류형규 · 대한건축학회 학술발표대회 논문집 · 2016

The pipe insulation standard in Korea are stated in 'Building mechanical equipment standard specification' which was amended in 2002 adding the rubber foam insulation standard. However, as compared with the conventional insulating materials, it was applied to a relatively thinner thickness standard. A rubber foam insulation is similar to other insulations in terms of thermal conductivity, but the emissivity of it is greater than others as it has the black(dark) color. The research findings are as follows. Due to the fact that the rubber foam insulations are thin, it is shown 54% ~ 94% more heat acquisition in the cold water pipes and 8% ~ 11% more heat loss in the hot water pipes. Therefore, it is necessary to improve the pipe insulation standard.

Cited by 0 works.