핀-관 열교환기에서 축열조를 이용한 제상특성
박천완, 백성현, 이창헌 et al. · 대한설비공학회 학술발표대회논문집 · 2016
Cold storage to agricultural products preservation is maintained with low temperature and high humidity which is formed by evaporator in refrigerator. Typically, heat sources of the defrost operation is supplied by using a heater, at this time, defrost power consumption accounts for 15% of the overall power consumption. Defrost characteristics of defrost system using thermal storage method are analyzed by flow path of working fluid for supply defrost heat using refrigeration system with 1/2HP compressor and replicate by using a water bath. Power consumption of the pump increases in proportion to the defrost time, showed the lowest power consumption defrosting time 4.3Wh at flow path of 7row. efrost system efficiency using thermal storage is the highest appeared in 12.3 in flow path of 7row and is lowest appeared from flow path of 2row to 4.26.