Метод диагностики обмоток трансформатора на наличие дефектов в виде короткозамкнутых витков

Ю. Н. Исаев, Г. А. Елгина · Современные проблемы науки и образования · 2014

In this paper the equivalent circuit of the transformer winding with closed loop like defect have been considered. Based on the assumption of having the magnetic coupling between the intact coil and the closed loop coil the model of diagnosis of the transformer winding have been proposed. It have been shown that when the scanning by probing pulse of transformer winding with closed loop type defect the voltage jumps has occur in the intact part of the winding. By tangents to the logarithm of voltage of intact winding the information about the parameters of a closed loop has extracted.An example of calculatingthe dependence plot which shows the fracture of current derivativeof the intactwindingwhen closed loop type defect is occur has been presented. Thegraphs of dependence of break of the current derivative for the scattering coefficient has been presented. It is shownthat the break of the currentderivative increases whenthe coincidenceof parameters ofintactandclose loop windings take place.