Снижение провалов напряжения при коммутациях преобразовательных агрегатов на тяговых подстанциях
Vasily Titovich Cheremisin, Кващук Валентин Андреевич, Карабанов Максим Александрович · Транспорт Российской Федерации. Журнал о науке, практике, экономике · 2011
The article looks at the problem of brownouts on the bus leads of 10 kV and 0,4 kV in the connection moment of rectifier units. In some cases it exceeded 30 per cent due to bumps during connection in the traction-feeding transformer, which was in such moments 5Inom. A method for reducing bumps was designed, and a device for simultaneous switching of traction-feeding transformer (USVT) was developed and tested on the existing traction substation of West-Siberian Railway, resulting in successful increase of power quality for non-traction consumers at moments of connecting the rectifier unit to the traction substation.
Cited by 0 works.