루버 핀-관 열교환기 착상 성능에 미치는 루버 제원 영향

박원걸, 김민지, Min-Soo Kim et al. · 대한설비공학회 2016년도 하계학술발표대회 · 2016

The present study predicted and verified local frost characteristics and total heat transfer rate of a louvered fin-tube heat exchanger with different louver geometry under frosting condition. They were predicted by applying segment by segment method for the heat exchanger. Reduced and locally different air flow rates of the segment were obtained by applying pressure drop and volume flow rate curve. The local frost thickness near leading edge was calculated by using maximum frost thickness on the louvered fin. Non-uniform frost characteristics, heat transfer rate, and pressure drop were predicted. Frost delay was developed as frost formed uniformly. The louver pitch was affected on the heat transfer rate of the heat exchanger more than that of louver angle.