가스엔진 히트펌프 시스템의 오일 및 냉매량 제어
신광호, 최송, 정호종 et al. · 대한설비공학회 동계학술발표회 논문집 · 2016
This study is describing a method for improving reliability and energy efficiency of GHP system. First of all, capacitance level sensor was evaluated for detecting oil level and in the oil separator. As the result of applying the oil level sensor in GHP system, it was confirmed that oil return operation was unnecessary. It provided a continuous heating operation under the sufficient presence of oil in oil separator. Therefore, GHP system applying the oil level sensor was able to reduce energy consumption as compared with the conventional system. Second of all, a control method for the refrigerant charge amount is performed using receiver. The energy efficiency was improved in the cooling and heating mode through changing refrigerant charge amount. The difference of refrigerant charge amount between optimal cooling and heating mode was about 27%, and it was controlled with relationship between high pressure and degree of subcooling.
Cited by 0 works.