히트펌프용 마이크로채널 열교환기 성능
박원걸, 김민지, 하야세 가쿠 et al. · 대한기계학회 춘추학술대회 · 2016
Frost forms on the surface of the heat exchanger as the heat pump operates below 0℃ under heating condition. Since frost blocks air flow through the heat exchanger, it increases air-side pressure drop and deteriorates heat transfer rate of the heat exchanger. Present study investigated frost characteristics and thermal performance of micro-channel heat exchanger using R-410A under frosting condition. Frost characteristics such as frost thickness, frost surface temperature etc were measured as well as transient heat transfer rate and pressure drop of the micro-channel heat exchanger under different frosting condition. Effect of non-uniformity of frost characteristics on the thermal performance of the frosted various micro-channel heat exchanger was investigated. Non-uniformity of frost growth caused decreasing of thermal performance of micro-channel heat exchanger.