Энергосбережение при отоплении в условиях Крайнего Севера
Игнаткин Иван Юрьевич · Вестник НГИЭИ · 2017
This article describes the use of a heat recovery system on the exhaust air a series-parallel circuit in the Far North. It needs two heat exchangers. Exhaust air enters the plenum and is distributed between the first and second recuperators stage. Recuperator first stage preheats the fresh outdoor air to a temperature of minus 20... 15 °C. The air heated in the first recuperator as supply enters the heat exchanger of the second stage and further heated exhaust air. Next, air is fed into the premises. Operating conditions of the first stage heat exchanger suggest icing exhaust channel, so if the outside temperature is below minus 20 °C, it operates in a cyclical «recovery» mode «defrosting». Tests were conducted in the areas of insemination and gestation period in breeding pig farm collective farm «Sibir» located at, Yakutsk, Markha area, village Kirzavod, Melioratorov Street, 1. The application of this system made it possible to reduce heating costs by 61,3 %; the development of production capacities without increasing the power boiler, fresh air is warming up to positive temperatures when the outdoor temperature down to minus 45 °C.