시뮬레이션에 기초한 공기열원히트펌프 용량변화에 따른 난방에너지사용 영향평가

도성록, 송현환, 이주훈 · 한국태양에너지학회 춘계학술발표회 논문집 · 2017

The purpose of this study is to evaluate heating energy consumption influenced by varying the capacities of an air-source heat pump (ASHP) system and to provide a suitable method for sizing the system capacity. In general, the smallest sized ASHP is selected to meet the corresponding heating and cooling loads of a residential building. An ASHP for general operation conditions mostly consumes electricity from a compressor component. If the outdoor temperature is below the thermal balance point temperature, however, the ASHP system requires operating an electric resistance component which is a supplementary heating system (also called a backup/auxiliary heating system). It causes excessive electricity consumption since the supplementary electric resistance is less efficient than the corresponding compressor. To minimize the supplementary electric resistance operation hours, therefore, it is required to determine the suitable system size by considering the electric resistance use. To achieve this evaluation, a computer simulation tool which is the DOE-2.1e program was used. To model the base-case building and system, this study followed the procedure of the International Energy Conservation Code (IECC) requirements. Six cases of the different system capacities were compared with their influences on energy consumptions. As a result, it was found that the range of the appropriate ASHP size for the base-case model (an area of 186 m2) was between 7.0 kW and 11.6 kW by avoiding excessive energy use from supplementary electric resistance heating with meeting required all space heating (i.e., no unmet hours existence).

Cited by 0 works.

Authors