진동대시험에 의한 전기판넬 내진 보강시스템의 내진성능평가
장정범, 이종림, 함경원 et al. · 한국지진공학회 춘계학술발표회 논문집 · 2009
Seismic reinforcing system is developed to prevent the damage of an electric panel, which is installed on the access floor, from the earthquake and its seismic capacity is verified through the shaking table test. In order to verify the seismic capacity of the seismic reinforcing system, real electric panel is used and two types of access floor such as wood panel and steel panel are considered. Also, two horizontal and one vertical earthquake input motions are calculated through the time history analysis intended to real structure and used to the tests. As a result of tests, electric panel which the seismic reinforcing system is installed, secured the seismic safety against the earthquake. Therefore, in case that seismic reinforcing system is applied to the electric panel on the access floor, the damage of electric panel can be prevented effectively from the earthquake.
Cited by 0 works.