사무용 건물의 베네시안 블라인드 설치 위치 계획을 위한 에너지 및 열 환경 평가에 대한 연구
최슬건, 류성우, 김철호 et al. · 한국태양에너지학회 춘계학술발표회 논문집 · 2017
The purpose of this study is to compare and evaluate the changes of annual cooling / heating, lighting load and thermal comfort according to the location of Venetian blind in office buildings. First, According to the blind position, we analyze the change of heat gain by comparing the conduction, convection, and radiation according to blind installation position using EnergyPlus. When the blind angle is 0 degree conduction of the interior blind, between glass blind and exterior blind are the same. For radiation, the interior blind and between glass blind were evaluated as the similar values, while radiation heat transfer of exterior blinds were rated 60% less than interior blind. In convection, the between glass blind was 50.3% and the exterior blind was 76% less than the interior blind. The total heat gain of interior blind was increased when compared with the between glass blind by 21%, when compared with the exterior blind by 40.4%. In conclusion, the interior blind was mostly effective for heating load and thermal comfort in winter and the exterior blind was most effective for cooling load and thermal comfort in summer. When the slat angle is fixed at 45 degrees in summer, the lighting and cooling load reduction of the interior blind is 9%, the reduction of between glass blind is 15% and the reduction of exterior blind is 22%.