상변화 유동을 이용한 회로 냉각부의 열전달 및 압력강하 특성 연구

김창훈, 이민주, 박창용 · 대한설비공학회 동계학술발표회 논문집 · 2016

Heat transfer and pressure drop characteristics in a heat sink was experimentally studied for electronics component cooling. The heat sink was made of copper and cartridge heaters were installed to simulate circuit heating. A test facility was set as a closed loop to make a two-phase flow conditions and condensate evaporated refrigerant. The refrigerant was FC72 due to its low saturation pressure and excellent electric stability. In the experimental test, average heat transfer coefficients reached up to 8 kW/m2K at the 200 W heating and mass flux of 50 kg/m2s which was equal to 0.4 liter/min volume flow rate. Dryout occurred at the vapor quality of 0.5 and heat transfer coefficient gradually decreased after the dryout. Heat transfer coefficient stated to increase even at the vapor quality less than 0 which was seemed to be caused by subcooled boiling. Pressure drop continuously increased as the increase of vapor quality.