에뮬레이션을 통한 차압 바이패스 밸브 적용 개별난방시스템의 유량 공급 특성 분석

문은진, 정창호, 여명석 et al. · 추계학술발표대회 · 2013

In general individual radiant heating system, supply water flow rate for individual room is designed under a peak load condition while all rooms are heated. When heating system operates under partial heating condition, it cannot operate as designed and supply water concentrated on heating rooms. In this study, we select the system applied for different pressure bypass valve as one of the alternatives for improving supply water flow rate problem and then, analyze characteristics of flow rate under partial heating conditions to evaluate application effect. This study utilizes an emulation method, which can complement the limitation of experiments and simulation. An emulator was designed to reflect the characteristics of the individual heating systems by replacing the component, which is difficult to evaluate through simulation with real hardware.

Cited by 0 works.

Authors