온도차 에너지를 이용한 냉방시스템 적용 사례 연구

김진욱, 류연수, 박미란 et al. · 한국태양에너지학회 춘계학술발표회 논문집 · 2015

Now a days, there has been a growing interest in alternative energy for greenhouse gas reduction and the reduction of fossil fuel consumption. Especially, it is unutilized energy that has been attracting attention as a community based alternative energy. Among them, temperature difference energy is abundant in nature and it does not give large influence on the environment. There are river water, treated sewage, seawater as temperature difference energy. As a case study for energy efficient heating and cooling with temperature difference energy, we would like to introduce the installation case of cooling system of the building using lake source in Cornell University, U.S.A. Finger Lake as a heat source is located in the New York State. Length of the lake is 61km, width is 1.6km, and maximum depth is 130m. In addition, the lake has water quantity of 2.5 billion gallon. Water intake pump was installed in a water depth 75m and the water will be arriving through HDPE pipe (Length: 3.22km, Diameter: 1.6m) to the tank of the heat exchange facility. Dimensions of the tank are 7.62m(Diameter), 13.716m(Length), and 10.668m(Depth). Water of the tank in heat exchange facility is sent to the seven heat exchangers using three pumps with 350 HP. Heat exchangers were usually operated with 200∼250 Psi. Current cooling system has been operating as a 0.1 kWh/ton-hour and it has been observed in the most efficient district cooling system in the world. In addition, carbon emissions per year was found to reduce the 25,400 ton.