서리부피 계산 방식을 통한 제상운전 시작시기 판단

류진우, 정융, 김귀택 et al. · 대한설비공학회 2017년도 하계학술발표대회 · 2017

In air heat pumps, frost naturally forms when the surface temperature of evaporator is lower than ice point. Judging the proper time of defrosting operation is one of the important task for air heat pump systems. Many different method were suggested previously but most of them are not cost-effective or realistic solution. In this study, a new method for determination of defrosting start time was suggested which calculates frost volume at evaporator. The frost volume was calculated with a dry bulb temperature and a humidity of outdoor air, evaporator temperature and degree of superheat (DSH). This method appropriately judge the start time of defrosting at the point within 15 minutes the system performance starts to decrease.