미세먼지 대응 고효율 필터가 적용된 혹한기 열 회수형 환기장치 개발

태경응, 명노훈, 강경모 et al. · 대한설비공학회 2017년도 하계학술발표대회 · 2017

Energy recovery ventilator (ERV) with application of pre-heater, by-pass and high efficient filter provides an opportunity to eliminate condensation in ventilator. However, building energy consumption increases for operating the heater. We applied to inner return damper rising air temperature without pre-heater. In the experiment, the condensation was not detected in -20℃. The highest CO 2 concentrations measured 991ppm operating return damper. When the high efficiency air filter was applied, power-consumption increased due to increasing the static pressure and the indoor PM10 concentrations decreased 28.4% less than without the filter. Applying to by-pass improve energy consumptions and indoor air quality.

Cited by 0 works.