An innovative HVAC system and system components have been proposed and applied to buildings to reduce energy consumption and maintain a comfortable indoor environment. Moisture control is an important factor in reducing the operation and maintenance costs in buildings and maintaining a comfortable indoor environment. The central purpose of this research is to develop a new desiccant-based energy recovery system, featuring integrated system design and analysis, as a dedicated outdoor air system for effective humidity control. The proposed system consists of two air?water heat exchangers with adsorbent material coated on the fins. It effectively employs directly heated desorption or directly cooled adsorption for the created adsorbent material. The system heat source uses unused energy, cogenerated hot water, and heated water from solar panels for the desorption process and cool water from cooling towers for the absorption process. This paper describes the results of an experimental investigation of the performance change for air humidification and dehumidification under outdoor air conditions. The results have shown that the temperature difference between the temperature of SA, OA is also increased. COP is increased OA temperature is lowered, for example, in the case of 5 o C, the COP was 0.57 OA temperature.