침실의 적정 환기량과 실간 환기량에 대한 연구

장현재 · 대한건축학회지회연합회 논문집 · 2010

Sick house syndrome (SHS) has been a social issue in Korea, and, after then, many people are interested in indoor air quality (IAQ). By the regulation on architectural equipment standards enacted on February 13, 2006, it became obligatory to install the ventilator, which has the ventilation rate above 0.7h-¹, in apartment houses for the improvement of sick house syndrome. The ventilation rates mentioned above was made by the consideration of VOCs concentration and formaldehyde concentration. However there are many pollutants in indoor space, and it is reasonable to decide ventilation under the investigations on those many kinds of pollutants. In this study, ventilation rate is recommended from the viewpoint of indoor concentration of carbon-dioxide. The recommended ventilation rate was investigated by field measurement and theoretical prediction formula. The ventilation rate, in this study, is recommended at 1.1h-1. and it does not contain infiltration rates but only by ventilator. Not only the concentration of air pollutant, but also the odor spreading in indoor space is a big issue in the field of indoor air quality. In this study, the air exchange rates between master's room and living room of dwelling unit of apartment house were investigated. Theoretical consideration on the data analysis for air exchange rates between rooms was conducted and the calculation of air exchange rates between rooms was tried. The air exchange rates between living room and master's room was calculated at 4.14CMH. For the further study on air exchange rates between rooms, it needs to study on the generalization under the conditions of temperature differency between rooms.