간이 실내 미세먼지 모델을 활용한 건물에서의 미세먼지 유입 및 이동 특성 평가
이병희, 이수환, 여명석 · 대한설비공학회 2017년도 하계학술발표대회 · 2017
The objective of this study is to analyze outdoor particle penetration and transport, and their impact on indoor air, in a building using a CONTAMW simulation. For the airflow and particle transport analysis, the building leakage, penetration coefficients, and deposition rates were determined by on-site experiments. The results of the airflow simulation in a cold winter show that outdoor air infiltrates through the lower part of building and exfiltrates from the upper part. The results of the particle simulation also indicated that the airflow characteristics, combined with the deposition rates, caused the lower floors of the multi-story building to be exposed to higher fine particle concentrations than the upper floors of the building. The study demonstrated that the CONTAMW simulation can be useful in analyzing the impact of outdoor particles on indoor environments through the identification of key particle transport parameters and validated airflow simulations.
Cited by 0 works.