초등학교의 실내공기 오염물질 제거 성능 분석

조성민, 박상태, 박철홍 et al. · 대한설비공학회 동계학술발표회 논문집 · 2017

According to forward studies, it was clearly confirmed that the most of teenager spend a great of their time in indoor spaces such as school. The purpose of this study is to analyze the indoor air pollutant removal performance of elementary school using air purifier and energy recovery ventilator. We had measured indoor air pollutants such as PM10 and CO2 at a couple of classrooms. The average concentration reduction effect of PM10 by energy recovery ventilator and air purifier was 30% in general classroom and 45% in experience room. The average concentration of CO2 was measured to be less than 1000ppm when energy recovery ventilator was operated.

Cited by 0 works.