파울링모니터를 이용한 냉각수계통 스케일억제 기술에 대한 연구

문전수, 박광규, 윤석원 · Applied Chemistry · 1999

A new conceptual fouling monitor has been deviced to estimate the performance of scale inhibition programs by measuring the fouling resistance of heat transfer surface sensitively. In the test condition of heat flux 12.5 W/㎠, cooling water linear velocity 1.5 m/sec, and a synthetic water of the Langelier Saturation Index (LSI) 2.5, the fouling resistance was measured as 0.0005 ㎡. ℃/W without any scale inhibitor, but the fouling resistance could decrease less than 0.0001 ㎡·℃/W with optimized scale inhibitors. The best test results could be obtained by feeding the combination inhibitors of HEDP (1-hydroxyehtylidene-1,1-diphosphonic acid) 5 ppm / polyacrylate 3 ppm or PBTC (2-phosphonobutane-1,2,4-tricarboxylic acid) 8 ppm/ polyacrylate 5 ppm into the test cooling water system.

Cited by 0 works.