고전압 및 방전공학 : LabView 기반 부분방전 분석장치의 설계 및 제작
차현규, 이정윤, Dae Won Park et al. · 2012
This paper dealt with the fabrication of a partial discharge (PD) analyzer for insulation diagnosis of power facilities like transformers, cables and gas-insulated switchgears. An analytic algorithm for the phase (φ), the magnitude (q), and the pulse count (n) of PD pulse was designed and a time-frequency (TF) map algorithm was applied in the system to eliminate noises by analyzing the time and the frequency component of signals. All the algorithms were operated by a LabView graphical program. The detection circuit consists of a coupling capacitor, a detection impedance, and a low noise amplifier. A plane-plane and a point-plane electrode system were fabricated to simulate different types of insulation defects. In the experiment, we could easily understand the characteristics of PD pulses using the prototype PD analyzer.
Cited by 0 works.