가변형 냉매 제어를 이용한 고밀도 서버랙 냉각장치

유원대, 박형준, 조용길 · 대한설비공학회 2017년도 하계학술발표대회 · 2017

Servers that provide clouding should be prepared for data usage changes. In case of web traffic, if the power consumption of the base unit generates heat and it can not be cooled down smoothly, the clouding system will be out of the operating temperature range of the IT equipment. The efficient power consumption of the data center requires CPU technology that maintains the performance of the underlying equipment at high temperatures and technology that efficiently cools the underlying equipment. The local cooling in the enclosure rack, which is cooled inside the rack, without draining the heat generated by the server's heat from the server rack, is the most efficient way to reduce power consumption. This paper describes server cooling system using variable liquid pump control which absorbs hot air generated by the server heat and then discharges the cooled air to the front of the server rack to discharge heat out of the rack. The server cooling unit uses PWM(Pulse width modulation) fan control to keep the cooling air temperature constant, and saves power energy by using stable cooling load and efficient power usage. By using the power consumption information of PDU(Power distribution unit) that supplies power to the server to effectively control the amount of cooling, stable operation of the cloud server equipment is ensured by fast and accurate cooling. This study controls the rotation of EEV(Electric expansion valve) and liquid pump with variable refrigerant flow control.

Cited by 0 works.