단일 개구에 있어서 문의 개폐에 따른 침기량 검토

이시환 · 대한설비공학회 동계학술발표회 논문집 · 2017

The purpose of this study was to evaluate the influence of swinging of a door at various speeds and air temperature differences between rooms on the infiltration rates. I measured the infiltration rates by dispersing sulfur hexafluoride, swinging door between an air-contaminated room and an adjacent room, and measuring the direction and velocity of the airflow. By comparisons of the results of measurement and CFD simulation, the CFD simulation model was validated. Using the CFD simulation model, fundamental design data were acquired concerning the influence of door opening.

Cited by 0 works.