오피스 건물에서 냉방 부하 특성에 따른 구체축열시스템의 동적 반응

임재한, 이윤선, 이겨레 · 한국태양에너지학회 춘계학술발표회 논문집 · 2018

Thermally activated building systems(TABSs) have been considered as energy efficient building systems in USA and European countries. This is because TABSs can use a lower temperature difference to achieve the same heating or cooling output compared to common HVAC systems because of its large surface area, which can improve the building energy efficiency and room thermal environment. In addition, TABS has been regarded as low-temperature heating and high-temperature cooling, employing low-energy heat sources and this can be used energy efficiently for building heating and cooling without extra thermal mass. However to utilize the high thermal capacities of the building structure for thermal energy storage, it is important to understand transient thermal response of TABS according to the actual load conditions in buildings. Because the TABS can handle only a limited amount of heating and cooling loads in buildings with a dynamic thermal response, it is also to increase the potential of the TABS utilization using control and operation strategies that consider different loads for each zone. In this study, the conventional TABS control and operation strategy was implemented using dynamic simulation to understand the transient thermal response of TABS. In results, TABS of the interior zone in office buildings can be used to meet the base cooling load for the entire year by considering the internal heat gains. TABS in perimeter zones can be used for removing the external load according to the separate control strategy.

Cited by 0 works.

Authors