ВИЗНАЧЕННЯ ДІАГНОСТИЧНИХ ПАРАМЕТРІВ ОЦІНКИ ТЕХНІЧНОГО СТАНУ ВИСОКОВОЛЬТНОГО ВИМИКАЧА

V.M. Kut'in, Oleksandr Yevheniiovych Rubanenko, С. В. Мисенко · The Scientific Issues of Ternopil Volodymyr Hnatiuk National Pedagogical University Series pedagogy · 2014

Reliability of power plants and substations is largely dependent on the reliability of high-voltage circuit breakers. Any change in current circles of power systems under normal and emergency modes perform switches which work in most cases depends on the technical condition of arc chutes and drive. To determine the technical state of the switch using the methods of continuous and periodic monitoring of the most informative form of representation which is depending on the velocity of the moving contact times. However, they receive on-strictions design features , such as the ground connection of sensors of angular and linear movement. Proposed for determining the technical state explosion chambers and drive - tachi method using overlay test high-frequency signal in the range that contains the contact chambers hexafluoride circuit breakers during their operation. To determine the set of parameters to assess technical state drive gas-insulated switches, a study of the switch during normal operation and abnormal operation of the switch actuator. Proposed as a diagnostic parameter that describes the technical condition of conjugated units drive time interval.

Cited by 0 works. doi:10.20535/1813-5420.3.2014.126183

Authors