화력발전소 온배수를 이용한 온실 난방 설계 시뮬레이션과 실제 가동에 따른 전력량 비교

박미란, 류연수, 김진욱 et al. · 한국태양에너지학회 춘계학술발표회 논문집 · 2015

Now a days, there has been a growing interest in agricultural use of thermal discharge from power plant as a strategy for agricultural competitiveness by restructuring of the industrial structure such as FTA. The greenhouse used as a heat source for heating of mango cultivation is located Seogwipo-si, Jeju Island.We compared operation with simulation using TRNSYS on electricity consumption. The greenhouse made double vinyl chloride film has 2 places (2,195m2, 1,617m2) and condition is to maintain day and night 24℃ as annual indoor temperature. Thermal discharge from power plant as heat source is transported about 500m through P.E.(o250) exposed piping and it become temperature rising through heat pump after heat exchange. After that, hot water is supplied to the greenhouse. Annual calorie necessary by design criteria is 478,291 kWh/yr and calorie necessary in winter season (December to February) is 176,981 kWh. Electricity consumption by operating is 273,848 kWh from December 2013 to November 2014. This shows when compared with the results of the simulation was approximately 1.75 times higher. This result is determined indoor temperature is lower than design temperature through adjustment of the shipping date and temperature control or operating time is short. As a result, greenhouse is determined that the operating time is subject to many influences on the basis of the farming management techniques.

Cited by 0 works.