삼중효용 흡수식 냉동기용 수직 단관 고온재생기의 성능 평가

정기문, 김선창, 전동순 · 대한설비공학회 2017년도 하계학술발표대회 · 2017

In this paper, the performance evaluation of a vertical single tube high temperature generator for triple effect absorption chiller was conducted. The band heaters, which supplies a heat flux of 5.6 to 27.8 kW/m2 were used. Experimental results show that the difference of concentraion increased with increasing heat flux. On the contrary, the solution flow ratio decreased withe increasing heat flux. Under the same heat flux condition, we obtained the higher difference of concentraion at a lower mass flow rate of LiBr aqueous solution.

Cited by 0 works.