수소 누출 시 제트화재 피해 범위에 대한 분석

강병우, 이택홍 · 2017

For commercialization of hydrogen refuelling station (HRS), we need to reduce the clearance distance for jet fire in the real entities in the HRS. Thus, we revisited the current regulations of clearance distance for jet fire in the law. The law in korea has been set up by replica of japan, not by our own scientific basis. Recently, sandia lab developed Hydrogen Risk Assessment Model (HyRAM) tools and we simulated a series of circumstances such as 10 to 850 bar with several leak hole sizes. In 850 bar with 10 mm diameter hole leak cases, it shows 4,981 kW/m2 at 12 m separation from leak source and 1,774 kW/m2 at 17 m separation from leak source. In 850 bar with 1 mm diameter leak hole, it shows 0.102 kW/m2 at 12 m separation and 0.044 kW/m2 at 17 m separation. Current law may be acceptable with 1 mm hole size with 850 bar.

Cited by 0 works.