일반건축물 용도별 냉방에너지 실사용량과 시뮬레이션 결과 비교분석에 관한 연구
박두용, 최슬건, 황동곤 et al. · 대한설비공학회 동계학술발표회 논문집 · 2018
Compare the unit cooling load of the design criteria for heating facility, the RTS simulation unit cooling load using the standard model, and the measured unit cooling actual usage. In the case of office buildings, the unit cooling unit of the design criteria for heating facility in 2003 was 132.6 W/m2, and the standard model simulation unit cooling unit applying the insulation standard in 2018 was analyzed as 120.0 W/m2. In the third year of 2016 ~ 2018, the maximum and average value of unit cooling actual use were 111.6 W/m2 and 53.0 W/m2, respectively. In the case of educational research buildings, the unit cooling unit of the design criteria for heating facility in 2003 was 122.1 W/m2, and the standard model simulation unit cooling unit applied to the insulation standard in 2018 was 113.5 W/m2. In the third year of 2016 ~ 2018, the maximum and average value of unit cooling actual use were 112.9 W/m2 and 54.3 W/m2, respectively.
Cited by 0 works.