디젤발전기의 내진용 방진베드 시스템의 내진성능평가
장성진, 전법규, 박동욱 et al. · 2018
The seismic performance of a vibration isolator bed system for emergency diesel engine generators was evaluated in this study. A shaking table test and numerical analysis were used for the evaluations. The ICC-ES AC156 test method was applied to the shaking table test, as recommended by ASCE 7. For inducing the input spectral acceleration, the generator was assumed at the highest location of a building. After the shaking table test, structural and functional rigidities were observed by visual inspection and functional testing. It was possible to evaluate the structural rigidity of the vibration isolator bed system for emergency diesel generators in greater detail through a numerical analysis.