This research evaluates the thermal and energy performance of the independent outdoor air system for reducing the latent cooling load of daycare center and enhancing the capability of midnight power storage tank in Jincheon eco-friendly energy town. In the cooling season of the Jincheon eco-friendly town, the chilled water is served to the buildings that contained town with thermal network for cooling the building. For producing the chilled water, the chilled water storage tank is used and the two heat pump system is operated with the ground source and sewage water source from the water treatment facility. In order to serve the chilled water through the daytime, the supply chilled water temperature is set at 10℃. That chilled water temperature can suit to the office building that has not much consider the latent cooling, however, the high latent cooling load building, such as daycare center, is not sufficient to cooling the building. In this research, we proposed independent outdoor air system for serving the ventilation and dehumidification with night-time operated storage tank as a parallel cooling system. The energy performance of the proposed system was estimated via simulation based on the experimental data of the test site.