다중 측정을 통한 실내 미세먼지의 공간 확산 특성분석
박한결, Haneul 최하늘Choi, Kyungmo 강경모Kang et al. · 한국태양에너지학회 춘계학술발표회 논문집 · 2019
Recently, Hazardous air pollution has made it important to keep indoor air quality clean. Analysis of the characteristics of PM2.5 distribution over time is required in order to reduce its concentration efficiently. Because, the rate of diffusion and emission rates is depending on the type of cooking. The majority of previous studies, the measurements were taken near the breathing zone, the living room center, and the gas stove to assess the health-risk. The research of multi-points measurement is insufficient due to the high cost of commercial measuring instruments. In this study, indoor air quality monitoring using low-cost sensors and TSI-DustTrak 8532 have been performed with different operating type of ventilation systems. Arduino-based PM2.5 sensors were built and installed five points in the kitchen and living room respectively. The results are as follows: The diffusion path of Case 1 was shown as the kitchen → ceiling of kitchen → between living room and kitchen → rear of living room → living room center → living room side. For Case 2 and 3 were similar in the detecting aspect in the ceiling of kitchen and then diffused to living room side. However, the between living room and kitchen in Case3 was analyzed to be the last, because of the constant auxiliary air supply. Also, It is necessary to consider the concentration near the ceiling as the highest concentration and the greatest rate of change among the spaces when after cooking. This study is expected to be applied for the optimal location of IAQ sensor and controlling the smart ventilation strategy to remove pollutants effectively.