설계인자가 수직밀폐형 지열 시스템 성능에 미치는 영향 분석
배상무, 김홍교, 남유진 · 한국태양에너지학회 춘계학술발표회 논문집 · 2018
It is necessary to develop high-efficiency energy technologies for energy saving and energy independence in the building sector. Among these high-efficiency energy technologies, vertical closed-loop geothermal systems can be expected to significantly provide annual stable performance by using underground heat source. However, it is affected by various design factors such as ground thermal properties, ground heat exchanger (GHX) characteristics, and system operation methods. In this study, performance of the system was quantitatively analyzed according to the design factors such as shape of the GHX, the flow rate, and between the U-tube distance. As the shape of the GHX is divided into a typical type and rib type, and EWT and heat pump COP were calculated according to flow rate and U-tube distance. As the result, EWT and heat pump COP of the rib type GHX increased by 10.5% and 1.1% respectively, comparing with the typical type GHX in the condition of U-tube distance 70mm and flow rate 40LPM.