메탈히터를 이용한 습식스프링클러 동결방지조치에 대한 실증실험 연구
남준석, Jae‐Gwan Park, 서상민 · 대한설비공학회 동계학술발표회 논문집 · 2018
If a wet sprinkler system is installed in a place where the fire intensity is high and the combustion is likely to expand in an environment exposed to the outside air, a metal heater may be used to prevent freezing. Metal heater was tested at outside temperature of -10 ℃ for 100 hours, and it was confirmed that metal heater was fully freeze prevention. Also, it was confirmed that the installation interval of the metal heater in the branch piping is proper 10 m.
Cited by 0 works.