In this study, the purpose is to identify the risks of the facilities of packaged hydrogen stations. As a risk identification method, failure mode & effect analysis (FMEA), a qualitative risk assessment, was used to analyze failure mode and effects of component of each facility. The analysis criteria were used to derive the risk priority number (RPN) using the 5-point method according to severity, incidence, and detectability. The study analyzed a total of 141 components of 23 types that can be identified on the design of the packaged hydrogen filling station. As a result, 683 types of failures and their causes and effects were identified. and the RPN was number of a total of 1,485. Of these, 10 failure types with a RPN value of 40 or more were deemed necessary. In addition, a list of failure types with a severity score of 5 was identified and analyzed.