지중열과 수열로 구성된 혼합열원 히트펌프 시스템의 난방성능분석
최홍식, 민경천, 손병후 et al. · 대한설비공학회 2017년도 하계학술발표대회 · 2017
The purpose of this study is to examine the initial cost down effects of geothermal and hydrothermal mixed source heat pump. Generally, construction cost of ground heat exchanger is higher than that of hydrothermal, especially surface water heat exchanger. Thus the natural or artificial pond nearby can be used as good heat source and sink. The residence building was selected for experiment and systematical data acquisition was conducted for analysis. From three cases of test, geothermal, hydrothermal and mixed(geothermal+hydrothermal), we could get following results. Heat pump COP in heating is 3.3 for mixed case and 2.8 for ground only. Also, system COP in heating is 2.5 for mixed case and 2.9 for ground only. Because of the over estimated circulation pump, COP shows a little low. Thus additional study needs for cooling performance and for raising of COP.