케스케이드 열펌프 급탕 유닛의 운전변수에 따른 성능특성에 관한 해석적 연구
송재현, 정해원, 박재우 et al. · 대한설비공학회 동계학술발표회 논문집 · 2011
A commercial heat pump system has been widely adopted in the buildings due to its higher energy efficiency. However, studies on the water heating heat pump are limited in the open literature. In this study, the simulation program for the design of a cascade water heating unit using R410A/R134a was developed. The accuracy of the program was verified comparing with the experimental data, showing the maximum deviation of 8.8%. The operating characteristics and COP of the cascade water heating unit were investigated analytically varying mass flow rate of water, water inlet temperature, and mass flow rate of R410A. The effects of these operating parameters on the system performance were analyzed and optimum control methods were also suggested.
Cited by 0 works.