실증을 통한 태양열 이용 흡착식 냉동기의 운전 특성 분석
이동규, 강기남, 이은주 et al. · 대한설비공학회 2017년도 하계학술발표대회 · 2017
This study aimed to verify capacity of the adsorption chiller under specific circumstances. Solar irradiation in South Korea is below average irradiation levels of the worldwide. Also, solar collecting areas over office and housing buildings in South Korea are not enough to make high temperature operating with solar thermal energy. Therefore, the small size of adsorption chiller is adaptable for dealing with solar thermal cooling system. The targeted zone is the lobby of first floor in Green Smart Innovation Center located in Mabuk-dong, Yong-ing si, South Korea. From September to October, four parameters are determined to verify performances of the adsorption chiller. The average radiation and cooling temperature of adsorption chiller are approximately 12.194kW and 55.58°C, and the average COPth is approximately 0.605. Therefore, small capacity of adsorption chiller is adaptable for cooling under certain restricted circumstances such as low levels of solar radiation and small collecting area. Also, domestic solar thermal system using adsorption chiller with respect using not high temperature has much great advantages of energy compared to without using middle-high temperature heats. Low cost analysis of using adsorption chiller has to be researched in next steps.