적층형 대형창고 스프링클러헤드 개발 및 성능실험

Kim Yoon Hung, 이준, 홍성호 et al. · 2019

Purpose: The purpose of this study is to develop a sprinkler head that can be controlled and initial suppressed by installing it in a rack–type warehouse. Method: Considering the spray radius and spray pattern, various deflectors were designed, and the spray angle, discharge characteristics and protection performance test was conducted, and these results were compared and analyzed. Results: An optimal sprinkler head was developed to protect full load, front side of a commodity with minimum water volume 115L/min. Conclusion: The developed head of K-115 and 1Bar pressure was tested with one tier storage confirming that the fire control is carried out without burning all the loadings. In addition, the vertical distance from the top of the load to the deflector shall be separated by 450mm and installed to allow sufficient discharge to the outer part of the commodity.

Cited by 0 works.

Authors