샌드위치패널 창고의 벽 천장 접합부 방호용 스프링클러설비 실험
Byung-Kug An, Kim Yoon Hung, 함은구 et al. · 2019
Purpose: The purpose of this study is to test the sprinkler performance to protect the wall and ceiling joints of the sandwich panel warehouse in case of fire. Method: Based on the field surveys, test was setup and combustibles were prepared. The sprinkler discharge tests were performed at the corner of the wall and right under the sprinkler head. Results: It has been found that operation of the K-80 closed sprinkler head prevents the ignition of the sandwich panel and therefore no damage to the joints of sandwich panels. To prevent skipping phenomenon, it is necessary to install the sprinkler head from the corner of the wall and to keep a minimum distance of 2.4m and a maximum distance of 3m. Conclution: A Standard Operation Procedure should be prepared to suppress and rescue of fire brigade for a sandwich panel warehouse protected by perimeter sprinklers preventing a ignition of core materials and control fire.